Successful exploitation of this vulnerability could result in memory corruption, a device crash, or a potential remote attack vector without the originating device receiving a CIP error indicating that the request could not be processed.
The following versions of Pyramid Solutions NetStaX EtherNet/IP Stack are affected:
| CVSS | Vendor | Equipment | Vulnerabilities |
|---|---|---|---|
| v3 9.8 | Pyramid Solutions | Pyramid Solutions NetStaX EtherNet/IP Stack | Stack-based Buffer Overflow |
Expand All +
An issue in the NetStaX EtherNet/IP Stack prior to v5.6.1 could allow a large Class 3 explicit-message request to exceed the application-side receive buffer without generating an error or warning. The result could be memory corruption, a device crash, or a potential remote attack vector without the originating device receiving a CIP error indicating that the request could not be processed.
Vendor:
Pyramid Solutions
Product Version:
Pyramid Solutions EtherNet/IP Adapter DLL Kit (EIPA): <v5.6.1, Pyramid Solutions EtherNet/IP Adapter DLL Kit with CIP Security (EIPA-SECURE): <v5.6.1, Pyramid Solutions EtherNet/IP Adapter Development Kit (EADK): <v5.6.1, Pyramid Solutions EtherNet/IP Adapter Development Kit with CIP Security (EADK-SECURE): <v5.6.1, Pyramid Solutions EtherNet/IP Scanner DLL Kit (EIPS): <v5.6.1, Pyramid Solutions EtherNet/IP Scanner DLL Kit with CIP Security (EIPS-SECURE): <v5.6.1, Pyramid Solutions EtherNet/IP Scanner Development Kit (ESDK): <v5.6.1, Pyramid Solutions EtherNet/IP Scanner Development Kit with CIP Security (ESDK-SECURE): <v5.6.1
Product Status:
known_affected
Relevant CWE: CWE-121 Stack-based Buffer Overflow
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet. Locate control system networks and remote devices behind firewalls and isolating them from business networks. When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.
| Date | Revision | Summary |
|---|---|---|
| 2026-09-03 | 1 | Initial Republication of Pyramid Solutions blog publication. |
此内容由惯性聚合(RSS阅读器)自动聚合整理,仅供阅读参考。 原文来自 — 版权归原作者所有。