Abstract:Operational disturbance monitoring in power networks requires decisions to be made from waveform windows as they arrive, rather than from completed records after the event. This study evaluates full-vector Wigner--Ville Distribution Slice (WVDS) spectra for sequential anomaly-onset detection in high-voltage grid-voltage waveforms. The approach keeps the bilinear midpoint interaction structure of the Wigner--Ville distribution and represents each 128-sample voltage window by a 128-dimensional slice spectrum, avoiding manually selected fault-frequency markers. WVDS is used with a baseline-normalized deviation (BND) score and is compared against the BND of Fast Fourier Transform (FFT-BND), raw-window autoencoders, FFT autoencoders, and WVDS autoencoders under the same thresholding and three-window persistence rule. A synthetic autoencoder--clustering teacher is used to select RTE fault records that start from an initially normal region and then transition to anomalous behavior. On the filtered test set, FFT-BND achieves the highest sensitivity, whereas WVDS-BND provides the lowest false-alarm operating point, reducing record-level pre-onset false alarms to 0.69%. The autoencoder comparison follows the same selectivity pattern: WVDS reconstruction decreases false alarms relative to FFT reconstruction but misses more examples. The results indicate that preserved WVD cross-term information can form a selective representation for online grid-waveform anomaly monitoring when false alarms are costly.