Abstract:To address the frequency stability challenges posed by the rising penetration of power electronics in power systems, HVDC-connected offshore wind power plants (OWPPs) are increasingly expected to provide inertial response and frequency containment reserve (FCR). In this paper, an improved holistic grid-forming (GFM) control is proposed, aiming to enhance the frequency support by coordinating the GFM controls implemented at all AC and DC terminals of an HVDC-OWPP system, without requiring communication. Firstly, the model of a typical HVDC-OWPP system is developed for control design. Accordingly, the proposed controllers are formulated, followed by an analytical tuning method, where the upper bound of the bandwidth at each AC or DC terminal is identified. Finally, simulations are conducted to verify the functionality and compare the performance with that of representative control configurations. The results show that the proposed holistic GFM control achieves faster response and thus more effective frequency support, while the utilization of the inherent energy storage of each converter is minimized, thereby supporting a new design philosophy for converter control in converter-dominated systems.